Specifications

Input: Two Alkaline “D” cell batteries required – Four supplied
rechargeable “D” cell batteries acceptable – Not included
Metering: Voltage: 1-65kVp(46kVrms), ±1% Accuracy, 0.1kV Resolution
Current: 0-150mAp(106mArms), ±1% Accuracy, 1uA Resolution
Tan Delta: 0.1Hz -0.01Hz, 5nF-10uF, 1.0 x 10-₄ Accuracy, 1.0 x
10-₅ Resolution
PC Interface: XBee 802.15.4 (wireless, ~30ft range)
PC Software: E-Link remote control and report generation software
Interconnect Cables: 88-5061 – 20ft/6.1m VLF output cable for use with V:F-34E
81-552 – 20ft/6.1m VLF output cable for use with VLF-65E
(Sold Separately)
Included Cables: 10ft/3m TD output lead terminated with red banana clip,
20ft/6.1m green/yellow test lead, 2in/51mm x 5in/127mm
toroid, 1 1/2in/38mm aluminum ball with banana socket
Size: TD Transducer w/ Tripod: 7in/152mm x 8in/203mm x
18in/457mm TD Carrying Case: 22.5in/572mm x 15in/381mm
x 11.75in/298mm

Condition Assessment Criteria

*All numerals are 10-₃ per Section 5, Tables 4 & 5 of IEEE 400.2-2013

 

Conditional Assesment No Action Required Further Study Advised Action Required No Action Required Further Study Advised Action Required No Action Required Further Study Advised Action Required
Insulation Type PE Based Insulation (PE, XLPE, WTRXLPE) Unidentified Filled Insulation (EPR) Mineral Filled Insulation (EPR)
Stability for TD Standard Deviation) < 0.05 0.05 to 0.5 > 0.5 > 0.1 0.1 tо 1.3 > 1.3 < 0.1 0.1 to 1 > 1
And Or And Or And Or
Tip Up (TD1.5U0 – TD0.5U0) < 5 50 to 80 > 80 > 5 5 tо 100 > 100 < 4 4 to 120 > 120
And Or And Or And Or
Mean TD @ UO < 4 4 to 50 > 50 > 35 35 tо 120 > 120 < 20 20 to 100 > 100